Burkert Type 8611 User Manual

Page 77

Advertising
background image

77

FunctionsoftheConfigurationLevel

Overview of the valve opening times of the Bürkert process valves depending on the actuator size and pilot
pressure:

actuator size [dn]

pilot pressure

Opening time for valve [s]

closing time for valve [s]

50

6

2

2

5
4

63

6

2

3

5

3

4

4

80

6

4

5

5

5

Table 28:

Valve opening times for Bürkert process valves

0 – 10 - flow-rate control with motor valve and 0 - 10 V control
(For schematic representation see “Figure 37: Example of a flow-rate control with 0 - 10 V control”)

Technical description:

• Motor ball valve with 0 - 10 V control.

• The max. process value change between closed and open position of the valve amounts to 20 l/min.

• The control range of the valve is not restricted:

VALV, MIN = 0, MAX = 10

(see chapter “12.17. VALV - Test function and setting of the control range”).

• According to the manufacturer, the opening and closing time are 90 s each.

Calculation for K

p1

:

100 %
20 l/min

K

p1

=

= 5 % (l/min)

·

100

The opening or closing time for the valve is taken into consideration by the reset time T

n

. As start value for T

n

about 60 - 70 % of the valve opening time can be taken.

2P – T

- Temperature control with open/closed valve

(For schematic representation see “Figure 39: Example of a 2-state temperature control with open/closed valve”)

Technical description:

• Solenoid valve.

• The process value change between closed and continuously opened position of the valve amounts to 10 °C.

• The time for the temperature change amounts to 20 s.

Calculation for K

p1

:

100 %
10 °C

K

p1

=

= 10 % °C

• The reset time T

n

can be set between 15 - 20 s.

• With the controller cycle time T

reg

the switching frequency of the valve can be influenced.

Recommendation: T

reg

= 0.5 - 0.25 T

n

english

Type 8611