FunctionsoftheConfigurationLevel

If the selected unit is changed in the

UNIT menu, the proportional gain [K

p

] must be adapted accordingly.

setting aid:

An unsatisfactory dynamic of the control is improved by increasing the aproportional gain [K

p

]. The fol-

lowing must be observed:

In the event of impermissibly high overshoots after set-point value jumps or in the event of an unstable
control, the proportional gain [K

p

] should be reduced.

12.13.2. examples for the setting and calculation of the

proportional gain [K

p

]

SCV

- pressure control using proportional valve

(For schematic representation see “Figure 33: Pressure control using proportional valve”)

Technical description:

• The control of the proportional valve is restricted to between 20 % and 90 %.

The control range of the valve is restricted as follows:

VALV, MIN = 20 %, MAX = 90 %

(see chapter “12.17. VALV - Test function and setting of the control range”).
The physical control range thus takes place between 20% and 90% of the valve position. The defined physical
range is set in the controller as 100%.

• The process value change amounts to 250 mbar.

Calculation for K

p1

:

100 %
250 mbar

K

p1

=

= 0,4 % mbar

PCV

- Quasi-continuous flow-control using process valve

(For schematic representation see “Figure 34: Example of a quasi-continuous control using process valve”)

Technical description:

• Bürkert process valve with actuator size 50 mm.

• The max. process value change between closed and open position of the valve amounts to 50 l/min.

• The flow change is done within the opening time of the valve. The opening time amounts of about 2 s (see

“Table 29: Valve opening times for Bürkert process valves”).

• The control range of the valve is not restricted:

VALV, MIN = 0, MAX = 0 (see chapter “12.17. VALV - Test

function and setting of the control range”).

Calculation for K

p1

and

K

p2

:

100 %
50 l/mn

K

p1

=

= 2 %

l/mn

The proportional coefficient for opening can also be used for closing.

The controller cycle time T

reg

can be set between 1 - 2 s. For slow control loops like temperature control T

reg

must be increased.

english