FunctionsoftheConfigurationLevel

12.13.1.

KP1, KP2 - setting the proportional coefficient

(proportional gain)

Depending on the actuating element selected in the

MODE menu (see chapter 12.3), the influence of the propor-

tional coefficient varies. It serves as proportional gain [K

p

] either for opening or for closing the actuating element.

calculation of the proportional gain [K

p

]:.

Calculation for continuous control (

MODE = SCV, 4 – 20 or 0 – 10):

The proportional gain is calculated by dividing the value for the manipulated variable change [∆%] by the value for
the process value change [∆PV].

∆%
∆PV

Manipulated variable change
Process value change

K

p

=

Depending on the selected actuating element in the

MODE menu the manipulated variable is scaled as follow:

MODE = SCV

0 % = Pulse duty factor 0 %

100 % = Pulse duty factor 100 % (relatively to PWM-

frequency)

MODE = 0 - 10

0 % = Manipulated variable 0 V

100 % = Manuipulated variable 10 V

MODE = 4 - 20

0 % = Manipulated variable 4 mA 100 % = Manipulated variable 20 mA

MODE = 2P - T

0 % = Valve closed

100 % = Valve (VLV1) open in relatio to time T

reg

(T

reg

= 100 %)

MODE = 3P - T

0 % = Valve 1 closed

100 % = Valve 1 (VLV1) in relatio to time T

reg

(T

reg

= 100 %)

0 % = Valve 2 closed

-100 % = Valve 2 (VLV2) in relatio to time T

reg

(T

reg

= 100 %)

MODE = PCV

0 % = Valve 1 closed

100 % = Valve 1 (VLV1) in relatio to time T

reg

(T

reg

= 100 %)

0 % = Valve 2 closed

-100 % = Valve 2 (VLV2) in relatio to time T

reg

(T

reg

= 100 %)

Speciality: The controller operates as a discontinous 2-state controller or 3-state controller if in the

MODE menu

as actuating element

2P - T or 3P - T is selected and the proportional gain K

p

is set to 9999 (independent from

decimal place). The parameters T

reg

and T

n

have no influence to the control..

The influence of the proportional value on the actuating element and the calculation of the proportional gain:

actuating
element
(selection in
MODE =)

influence proportional
coefficient

calculation of the
proportional gain
[K

p

]

value range

SCV
4 – 20
0 – 10

Proportional gain K

p1

for

opening and closing the
actuating element

∆%
∆PV

K

p1

=

0.001 – 9999
Changing the decimal places

Press the ENTER key to select KP1 or KP2.

Use the arrow key to move to the left until the
decimal place flashes.

Now use the up arrow key to position the
decimal place at the correct place and
confirm with ENTER.

PCV
2P – T
3P – T

Proportional gain K

p1

for

opening the actuating
element

∆%
∆PV

K

p1

=

PCV
3P – T

Proportional gain K

p2

for closing the actuating
element

∆%
∆PV

K

p2

=

Table 27:

KP1, KP2 - Proportional gain