FunctionsoftheConfigurationLevel

display

description

2_P

Selection for the binary output with the function as 2-state controller.

REL

The 2-state control is implemented relatively to the set-point value depending on the
deviation between set-point value and actual process value.
If the set-point value is changed, the control limits are adapted automatically.
See “Figure 66: B_O1, 2_P; 2-state control relatively to the set-point value”
HYHI: Upper hysteresis
HYLO: Lower hysteresis
Value range:

HYHI, HYLO >= 0

Measuring unit: absolute, like defined in

UNIT

SP

The switching of the outputs is done relatively to the set-point value (

SETP) between

the limit values (

SPHI) and (SPLO). This function can be used e. g. for opening

or closing an additional open/closed valve for extending the working range of the
control valve.
SPLO: Lower switching threshold referred to set-point value
SPHI: Upper switching threshold referred to set-point value
Measuring unit: absolute, like defined in

UNIT

ABS

2-state control between the fixed limit values (

PVHI) and (PVLO). Depending on the

selected control variable and measuring unit following can be selected:
FLOW: 2-state control of flow
PRES: 2-state control of pressure
TEMP: 2-state control of temperature
LEVL 2-state control of level
VAL: 2-state control of conductivity, pH-value, concentration or process values

without indication of units (UNIT = NU)

PVHI: Upper switching threshold referred to analog process value.
PVLO: Lower switching threshold referred to analog process value.

(

PVHI >= PVLO)

The 2-state control between the limit values

PVHI and PVLO can, for example, be

used for the filling level control in a tank.

DLY

Time in sec for that the deviation must constantly be present.

INV

Effective direction between the process value and the opening of the valve
YES: Inverted control direction
NO: Direct control direction (not inverted)
Example: The control is inverted, if the displayed process value decreases when the
valve opens.

HIGH

Binary output active at voltage of 24 V.

LOW

Binary output active at voltage of 0 V.

Table 33:

Display B_O1, configuration as 2-state controller