48

FunctionsoftheConfigurationLevel

12.3.1.

RATI - selection of external sensors for ratio control

A ratio control can easily be implemented by combining the compact controller Type 8611 with flow-rate fitting
S030 and a second flow-rate sensor.

In a ratio control, the controlled flow-rate Q

1

is adapted to the uncontrolled flow-rate Q

2

so that it corresponds to

a specified mixture ratio.

The flow-rate is measured for Q

1

using the Bürkert flow-rate fitting of Type S030

for Q

2

using a second external flow-rate sensor.

The following relation exists between Q

1

and Q

2

:

Q

1

= RFAC · Q

2

Q

1

: controlled flow-rate

Q

2

: uncontrolled flow-rate

RFAC: ratio factor

(for selection see chapter “11.6. RFAC - Ratio factor default for ratio
control”)

Example of a ratio control:

Selected ratio factor RFAC:

4, 00

Flow-rate Q

2

:

20 l/h

Control of Q

1

to:

20 l/h · 4 = 80 l/h

Schematic representation:

Controller setting:
MODE = RATI, FREQ, 4 – 20, FREQ

8611

Flow-rate Q

1

controlled

Flow-rate Q

2

uncontrolled

Flow-rate fitting,

Type S030

Fluid mixture

Q

2

Manipulated variable 4 - 20 mA

Frequency (

FREQ)

Figure 28:

Ratio control using process controller Type 8611 (assembly directly on flow-rate fitting Type S030).

english

Type 8611