FunctionsoftheConfigurationLevel

Settings in the menu:

Continue with
selection of actuating element
(see chapter 12.3.2 to
chapter 12.3.6)

select frequency input for sensor input Q

2

select standard signal for sensor input Q

2

MODE

selection of control variable

0001

CODE

RATI

NORM

**

)

FREQ

*

)

*

)

FREQ: The sensor-specific K-factor is entered in the

KFAC menu.

**

)

NORM: The scaling of the standard signal is selected in

the

S_IN menu

Figure 29:

RATI; Setting the ratio control

particularity of the control cabinet model!

In the control cabinet model, the standard signal input is available for Q

1

in addition to the frequency input.

However, for the inputs Q

1

and Q

2

, a standard signal (

NORM) can only be assigned once.

If the standard signal was selected for sensor input Q

2

(

MODE, RATI, NORM) only frequency is available

when selecting the process value input Q

1

.

Example:

selection of sensor input Q

2

selection option for process value input Q

1

FREQ (frequency)

FREQ (frequency) or NORM (standard signal)

NORM (standard signal)

FREQ (frequency)

Table 15:

Select NORM/FREQ for sensor input and process value input

english

Type 8611