See chapter 12.3.4) – Burkert Type 8611 User Manual

Page 55

Advertising
background image

55

FunctionsoftheConfigurationLevel

Setting the minimum control time in the menu:

Selection of
control variable

Continue with
selection of process value input
see Figure 27

MODE

enter minimum control time for control valves

0001

CODE

PCV

0005

TMN1

0005

TMN2

Figure 36:

PCV; Enter minimum control time for control valves

12.3.4.

4–20 / 0-10 - continuous control with 4 - 20 ma or 0 - 10 V

standard signal

This function can be used for operating control valves (e.g. motor valve, positioner) via the analog output using
the control for 4-20mA or alternatively 0-10V standard signal.

Example of a typical use, the flow-rate control in conjunction with a flow-rate sensor and an electric motor control
valve, see Figure 37.

8611

Controller

Set-point value

M

10

0

Pos

8611

Process value

Manipulated variable 0 - 10 V

Flow-rate fitting

Type S030

Controller setting:
MODE = F, 0-10, FREQ

Figure 37:

Example of a flow-rate control with 0 - 10 V control

Setting the continuous control with standard signal in the menu:

Selection of
control variable

Continue with
selection of process value input
see Figure 27

MODE

0001

CODE

selection of standard signal

4 – 20

0 – 10

Figure 38:

MODE; Setting the standard signal

english

Type 8611