See chapter 12.3.5) – Burkert Type 8611 User Manual

Page 56

Advertising
background image

56

FunctionsoftheConfigurationLevel

12.3.5.

2P – T - Quasi-continuous 2-state control with open/

closed valves

This function can be used to implement quasi-continuous controls using open/closed valves.

Here, unlike in purely open/closed controls that only provide for the states open or closed, the control time for the
opening or closing is varied proportionally to the set-point/actual value deviation. The valves are controlled via the
transistor output of the controller.

T

8611

Pt 100

Controller setting:
MODE = T, 2P – T, NC, PT

NC valve

Figure 39:

Example of a 2-state temperature control with open/closed valve

Setting the quasi-continuous 2-state control in the menu:

Selection of
control variable

MODE

0001

CODE

selection of
operating principle

enter
minimum
control time

selection of
2-state control

Continue with
selection of process value input
see Figure 27

2P – T

NC

VLV1

NO

VLV1

0001

TMN1

Figure 40:

2P – T; 2-state control / operating principle

display

description

2P – T

Quasi-continuous 2-state control with time-proportional control for opening and closing.

VLV1

Control of valve 1 (output

BO3)

NC

Valve with operating principle "closed with no current" (normally closed).

NO

Valve with operating principle "opened with no current" (normally open).

TMN1 Minimum control time in ms

Table 17:

Display 2P – T; quasi-continuous 2-state control / operating principle

english

Type 8611