Electrical installation, 2 electrical installation – Burkert Type 8695 User Manual

Page 31

Advertising
background image

31

Electricalinstallation24VDC

9.2

electrical installation

configuration

circular plug (m12 x 1, 8-pole):

6

1

7

5

4

3

2

8

Figure 18:

Circular plug M12 x 1, 8-pole

pin

Wire color

2)

Designation

Configuration

external circuit / signal level

1

white

limit switch top

IN 1 (=Top)

1
2

GND

+ 24 V

IN 1
IN 2

{

100K

2

brown

limit switch bottom

IN 2 (=Bot)

3

green

Supply voltage

GND

3
4

GND
24 V

4

yellow

Supply voltage +

24 V DC

5

grey

Valve control unit +

Valve +

5
6

24 V
GND

6

pink

Valve control unit -

Valve -

7

-

not used

8

-

not used

Table 3:

Connection with circular plug-in connector

Connect the control head according to the table.

When the supply voltage is applied, the control head is operating.

To read in the end positions of the valve, start the teach function (see “9.3 Teach function (calibrating the end
position)”

).

2)

The indicated colors refer to the connecting cable available as an accessory (919061).