1 starting the teach function – Burkert Type 8695 User Manual

Page 55

Advertising
background image

55

DeviceNetinstallation

11.12.1 starting the teach function

Danger!

Danger due to the valve position changing when the teach function is running.

When the teach function is running under operating pressure, there is an acute risk of injury.

▶ Never run the teach function while a process is running.

▶ Secure system from unintentional activation.

The teach function can be started and read out via the “

Teach function” attribute.

User 2 can receive information through the read out:

• firstly he is informed whether the teach function is completed.

• after the teach function is completed, the result of the function can be read out.

Access occurs acyclically via Explicit Messages with the

Set_Attribute_Single (write access) service and the

Get_Attribute_Single service (read access).

1 data byte for teach function:
(Attribute address: class 150, instance 1, attributes 8)

Set_Attribute_Single:

Bit

mode

Value assignment

Bit 0

Teach function

0 Start teach function

Bit 1

not used

– (only read access permitted)

Bit 2...7

not used

0 always

Table 21:

Set_Attribute_Single

Get_Attribute_Single:

Bit

mode

Value assignment

Bit 0

Teach function

0 Teach function is running
1 Teach function is completed

Bit 1

Result of teach function
(available after end of teach function)

0 Teach function successfully completed
1 Teach function defective

Bit 2...7

not used

0 always

Table 22:

Get_Attribute_Single