12 teach function (calibrating the end position) – Burkert Type 8695 User Manual

Page 52

Advertising
background image

52

DeviceNetinstallation

11.11 configuration of the safety position of pilot valves

for bus error

If a bus fault occurs, the bus LED may assume the “Green flashing”, “Red flashing” or “Red” status.
(For a description see “Status of the bus LED”, page 57)

The valve safety position and safety module attributes can be used to configure the pilot valve in the event of a bus fault.

If a bus fault occurs, the configuration data of the pilot valves can be accessed acyclically via Explicit Messages.

• The

Get_Attribute_Single service stands for a read access of the configuration data.

• The

Set_Attribute_Single service stands for a write access of the configuration data.

1 data byte for safety mode:
(Attribute address: class 150, instance 1, attri-
butes 7)

1 data byte for valve safety position:
(Attribute address: class 150, instance 1, attributes 6)

Bit

mode

Value assignment

Bit

solenoid valve

Value assignment

Bit 0

Character-
istics in event
of bus fault

0 Output safety position
1 Retain last valve
position

Bit 0

Y1
(Pilot valve 1)

0 Pilot valve 1 OFF
1 Pilot valve 1 ON

Bit 1... not used

0 always

Bit
1...7

not used

0 always

Bit 7

Table 19:

data byte for safety mode

Table 20:

data byte for valve safety position

11.12 Teach function (calibrating the end position)

The teach function can be used to automatically determine and read in the end positions of the actuator.

For the bus variant DeviceNet, the teach function can also be started via the bus protocol (see “11.12.1
Starting the teach function”
).

Danger!

risk of electric shock.

▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.

▶ Observe applicable accident prevention and safety regulations for electrical equipment.

necessary requirements:

Before you can actuate the each function, you must

• mount the control head on the actuator,

• connect the supply voltage and

• connect the compressed-air supply.

english

Type 8695

Advertising