50

DeviceNetinstallation

Procedure:

noTe!

Breakage of the pneumatic connection pieces due to rotational impact.

▶ When unscrewing and screwing in the transparent cap, do not hold the actuator of the process valve but the

connection housing.

Open the control head: turning the transparent cap anti-clockwise.

Body casing

Connection housing

Actuator

Transparent cap

Figure 41:

Open control head

Set the DIP switches according to the following tables.

noTe!

Damage or malfunction due to penetration of dirt and humidity.

▶ To observe degree of protection IP65 / IP67, screw the transparent cap in all the way.

Close the device (assembly tool: 674078

8)

).

Settings of the Devicenet address

MAC ID - Medium Access Control Identifier:

[DIP 1=off=0 / DIP 1=on=1 / MAC ID=DIP 1*2

0

+DIP 2*2

1

+...+DIP 6*2

5

]

Dip 1
[20=1]

Dip 2
[21=2]

Dip 3
[22=4]

Dip 4
[23=8]

Dip 5
[24=16]

Dip 6
[25=32]

mac iD

off

off

off

off

off

off

0

on

off

off

off

off

off

1

off

on

off

off

off

off

2

...

...

...

...

...

...

...

off

on

on

on

on

on

62

on

on

on

on

on

on

63

Table 15:

Settings of the DeviceNet address

8)

The assembly tool (674078) is available from your Bürkert sales office.

english

Type 8695

Advertising