26

Start-up 24 V DC

Typ 8750

11.2. define basic settings

Setting the input signal

procedure:

Key

Action

Description

MENU

MENU

Press

for 3 s

(countdown in the
display)

Switching from
process level

setting level

/ Select

INPUT

Selection

INPUT menu

MENU

ENTER

Press

Change to

INPUT menu

/

Select 4 - 20 mA, 0 - 20
mA, 0 – 10 V or 0 – 5 V

Select the input signal

MENU

SELEC

Press

Specifying the input signal

MENU

EXIT

Press

Exit

INPUT menu

MENU

EXIT

Press

Switching from
setting level

process level

Tab. 17: Setting the input signal

INPUT

MENU

SELEC

4-20 mA

MENU

EXIT

MENU

ENTER

0-20 mA

0-10 V

0- 5 V

Fig. 15: Operating structure INPUT (select input signal)

You must exit the main menu by pressing the left selection
key

MENU

EXIT

before the modified data is saved to the

memory (EEPROM). During the save process, the save symbol
is indicated on the display.