Additional fmr functions, M3/min – Burkert Type 8750 User Manual

Page 30

Advertising
background image

30

Additional FMR functions

Typ 8750

11.4.1. change the process set-point value

procedure:
1. Set the set-point value default on the setting level:

In the main menu (MAIN), select the

F.CONTROL function

F.CONTROL

ENTER

SETUP

ENTER

SP-INPUT

intern

SELEC

Use the

MENU

EXIT

key (press 4 x) to return to the process level.

2. On the process level, manually change the process set-point

value:

Use the arrow keys to select the
display for the process set-point value (SP).

MENU

PV

PV (t) INPUT

sp

30.0

m3/min

Press

MENU

INPUT

key.

Enter the process set-point value (see image below).

ESC

+

<-

OK

SET VALUE

sp:

[m3/min]

70.0

+

070.

0

Accept set value

Return without change

Change by one position to the left

Increase number

Changeable number

Fig. 17: Enter values

12. addiTional fmr funcTions

Overview

CHARACT

CUTOFF

DIR.CMD

DIR.ACT

SPLTRNG

14)

X.LIMIT

X.TIME

X.CONTROL

F.CONTROL

SECURITY

SAFEPOS

SIG.ERROR

BINARY.IN

OUTPUT

CAL.USER

SET.FACTORY

SER. I/O

EXTRAS

SERVICE

SIMULATION

DIAGNOSE

ADD.FUNCTION

EXIT

ENTER

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Fig. 18: Overview of FMR auxiliary functions

english