DeviceNet start-up

Typ 8750

14.2. configuration of the process data

The following components are required for the configuration:
• Software suitable for the configuration. For example RSNetWorx for

DeviceNet (Rev. 4.12.00).

• ESD file (is on the supplied CD).

transferring process data
The process data is transferred via an I/O connection. 5 static input
and 2 static output assemblies can be selected for the transfer. In these
assemblies selected attributes are combined in one object.

selecting the process data
The process data is selected by setting the device parameters during
initialization of the I/O connection according to the DeviceNet speci-
fication. The following device parameters can be set:
• Active Input Assembly and Active Output Assembly or
• Produced Connection Path and Consumed Connection Path

- if supported by the DeviceNet Master/Scanner -.

14.2.1. static input assemblies

name

address of data
attribute of the
assemblies for
read access. class,
instance, attributes

format of the data
attribute

POS+ERR
(factory setting)

4, 1, 3

Byte 0: POS low
Byte 1: POS high
Byte 2: ERR

POS+CMD+ERR 4, 2, 3

Byte 0: POS low
Byte 1: POS high
Byte 2: CMD low
Byte 3: CMD high
Byte 4: ERR

PV+ERR

4, 3, 3

Byte 0: PV low
Byte 1: PV high
Byte 2: ERR

PV+SP+ERR

4, 5, 3

Byte 0: PV low
Byte 1: PV high
Byte 2: SP low
Byte 3: SP high
Byte 4: ERR