Safety end positions, Error messages – Burkert Type 8750 User Manual

Page 46

Advertising
background image

46

Safety end positions

Typ 8750

15. safeTy end posiTions

actuator

system

designation

safety end positions after

failure of the auxiliary power

electrical

pneumatic

up

down

single-acting

Control

function A

down

pilot-controlled
control system:

down

direct-acting

control system:

not defined

up

down

single-acting

Control

function B

up

pilot-controlled
control system:

up

direct-acting

control system:

not defined

up

down

double-acting

Control

function I

down / up

(depending
on the con-

nection of

the control

cables)

not defined

Tab. 30: Safety end positions

16. error messaGes

General error messages (display only for external set-point value and
with activated

SIG.ERR).

display

cause

remedial action

min

Minimum input value has
been reached.

Do not reduce
value further.

max

Maximum input value has
been reached.

Do not increase
value further.

SP error

Signal error set-point value
process controller

Check signal

P1 error

Signal error actual value P1
Flow control system

Check signal

P2 error

Signal error actual value P2
Flow control system

Check signal

invalid code

Incorrect access code.

Enter correct
access code.

EEPROM
fault

EEPROM defective.

Not possible,
device defective

Tab. 31: General error messages

english