Error messages

Typ 8750

BUS timeout
is displayed
approx. every
3 seconds

I/O connection
timeout.

An I/O connection is in the
TIME OUT state.

New connection estab-
lishment by master;
ensure that I/O data is
transferred cyclically or, if
COS confirmed, that cor-
responding Acknowledge
messages are sent by the
master.

BUS critical err
is displayed
approx. every
3 seconds

Critical bus
error.

Other device with the same
address in the network or
BUS OFF due to communi-
cation problems.

Change address of the
device and restart device.

Error analysis in the
network with a bus
monitor.

Tab. 36: Error messages DeviceNet

16.2. other error messages

display

cause

remedial action

POS = 0
(bei CMD > 0 %) or
POS = 100 %,
(when CMD < 100 %).
PV = 0
(when SP > 0) or
PV = PV
(when SP > SP ).

Sealing function
(

CUTOFF) is uninten-

tionally activated.

Deactivate sealing
function.

Applies only to devices
with binary output:
Binary output does not
switch.

Binary output:
• Current > 100 mA
• Short circuit

Check binary
output connection.

Tab. 37: Other error messages

english