DeviceNet start-up

Typ 8750

BUS FAIL

Activate or deactivate approach of the safety
position

SafePos off

The actuator remains in the position which cor-
responds to the set-point value last transferred
(default setting).

SafePos on

If there is a fault in the bus communication, the
behavior of the actuator depends on the acti-
vation of the

SAFEPOS auxiliary function.

SAFEPOS activated:

The actuator moves to the safety position
which is specified in the

SAFEPOS aux-

iliary function.

SAFEPOS deactivated: The actuator moves to the safety end

position which it would assume if the elec-
trical and pneumatic auxiliary energy failed.
See Chapter “15. Safety end positions”.

OK

Address 0

BAUD RATE

BUS FAIL

125 kBd

SafePos off

250 kBd
500 kBd

SafePos on

BUS.COMM

ENTER

INPUT

Enter
value

EXIT

EXIT

ENTER

ENTER

+

Input device
address.
Adjustment range:
0 – 63

18)

Selection
of the baud
rate

Activate /
deactivate
approach
of the
safety
position

SELEC

SELEC

EXIT

Fig. 24: Operating structure BUS.COMM - DeviceNet