6. sysTem descripTion

6.1. General description

To determine and control the volumetric flow rate, the pressure drop
over the control valve is measured continuously by the two pressure
sensors. This pressure difference and the valve flow characteristic
are the parameters used to determine the volumetric flow. This mea-
sured volumetric flow is compared with the set point – internally via
display/keyboard or externally via standard signal or bus protocol –
evaluated in a PID controller and set on the position controller as the
new set point.

The system consists of:
• Control valve Type 2712 with process controller Type 8693
• Two pressure sensors Type 8323

Options:
• Binary input
• Analog feedback
• 2 binary outputs
• Bus communication (PROFIBUS DP or DeviceNet)

Other:
• The flow controller is supplied with a factory setting.
• The device is operated via 4 function keys and a display.
• The valve seat can be exchanged.

6.2. structure

Process controller Type 8693

Actuator control valve Type 2712
Signal line from pressure sensor to
the process controller

Valve body control valve
Type 2712

Pressure sensor Type 8323

Flange acc. to
DIN EN 1092-1

Fig. 1:

Structure

6.2.1. action diagram of the fmr

Flow

controller

(FMR)

Type

8750

PV

P1

P2

Pressure P1

Pressure P2

Temperature T

(Option)

Kv value

Fig. 2:

Action diagram

english