Devicenet start-up, Settings in bus.comm – Burkert Type 8750 User Manual

Page 39

Advertising
background image

39

DeviceNet start-up

Typ 8750

name

description

identifier

PDO:ERR

Reset error display
If the value > 0,

ERR is reset.

GSD file:
PDO: ERR
Identifier (HEX):
81, 00, 17

PDO:
MTMP

Medium temperature
Temperature in °C on 1 °C exactly
Value range 0 °C – 150 °C

GSD file:
PDO:MTMP
Identifier (HEX):
81, 40, 18

PDO:
CONact

0: Positioner
1: Process controller

GSD file:
PDO:CONact
Identifier (HEX):
81, 00, 19

Tab. 25: Process Data Output, PROFIBUS DP

14. deViceneT sTarT-up

procedure:
• Perform the automatic adjustment (

X.TUNE) of the process controller.

• Add the

F.CONTROL auxiliary function to the main menu using the

configuration menu (

ADDFUNCTION) and create settings.

• Make settings in the

BUS.COMM function.

• Configuration of the process values.

14.1. settings in BUS.COMM

Address 0

Enter a device address (value between 0 and 63)

BAUD RATE

Selection of the baud rate

• The baud rate can be changed either by pressing the operator keys

on the device or via the bus.

• A change has no effect until a reset (send a reset message to

the identity object) or power up is implemented. This means if the
changed baud rate attribute is accessed before a reset or power up,
the read (changed) value does not agree with the still current baud
rate (to be changed) of the network.

Select 125 kbit/s, 250 kbit/s or 500 kbit/s