DeviceNet start-up

Typ 8750

This I/O connection can be used to transfer the attributes described
in more detail in the following “Tab. 29” as output process data.
Nevertheless, by using this address data, the attributes combined
in the assemblies can also be accessed acyclically at any time via
Explicit Messages.

name

description of the output data
attributes

attribute
address class,
instance,
attribute; data
type, length

INP

Set-point position
Set-point value of process con-
troller as ‰. Value range 0 – 1000.
In "pure" position controller
mode (

F.CONTROL inactive)

the transfer of the INP set-point
position is required; as a process
controller (

F.CONTROL active)

the transfer of INP is not possible.
If the value is too small or too large,
the last valid value is used and is
indicated in

ERR with HEX 14.

111, 1, 58;
UINT, 2 byte

name

description of the output data
attributes

attribute
address class,
instance,
attribute; data
type, length

SP

Process set-point value
Set-point value of process con-
troller in physical unit (as set in the
menu

P.CO INP or P.CO SCAL),

max. value range -999 – 9999,
depending on internal scaling.
If the value is too small or too large,
the last valid value is used and is
indicated in ERR with HEX 15.

120, 1, 2;
INT, 2 byte

MTMP

Medium temperature in °C

120, 1, 9;
INT, 2 byte

PCONact P.CONTROL active

120, 1, 10;
USINT, 1 byte

Tab. 29: Output data attributes; DeviceNet