CONTREX ML-Drive User Manual

Page 149

Advertising
background image

C - 13

CP-73

CONTROL MASK

The Serial Communications can control some of the logic input functions. Enter the number for
the required functions in Control Mask (CP-74), as listed below.

0 = F-Stop only
1 = F-Stop, Run, R-Stop
2 = F-Stop, Master/Follower, Setpoint Select
3 = All of the above

CP-74

DRIVE ENABLE LOGIC

Drive Enable Logic (CP-74) determines which conditions of the Ramped Reference (MP-46) and
the feedback will control the Drive Enable digital output.

Enter "0" to deactivate the Drive Enable digital output (output high) when the Ramped

Reference is zero, and activate the Drive Enable digital output (output low) when
the Ramped Reference is not zero.

Enter "1" to deactivate the Drive Enable digital output when both the Ramped

Reference and the feedback are zero, and activate the Drive Enable digital
output when both the Ramped Reference and the feedback are not zero.

CP-80

RMS CURRENT LIMIT

RMS Current Limit (CP-80) determines the level at which the ML-Drive will limit the motor
armature's RMS current. The ML-Drive achieves this limit by reducing the phase angle firing.
For additional information about current limit, refer to

Installation/Setup: Calibration

, page 2-17.

CP-81

PEAK CURRENT LIMIT

Peak Current Limit (CP-81) determines the level at which the ML-Drive will limit the motor
armature's RMS peak current. The ML-Drive achieves this limit by reducing the phase angle
firing. For additional information about current limit, refer to

Installation/Setup: Calibration

, page

2-17.

MP-82 MOTOR CURRENT

Motor Current (MP-82) displays the value, in amps, of the motor armature's RMS current.