Alarm, Warning, Auxiliary dc power – CONTREX ML-Drive User Manual

Page 28

Advertising
background image

2 - 14

Alarm

(J4 pin 17)

By entering alarm Control Parameters, you can establish circumstances under which
the ML-Drive will alert you to potential operating problems. The alarm can be wired to
activate a warning light, a warning sound, or to shut down the system under specified
conditions. Alarm Format (CP-10) determines which alarm conditions will activate the
Alarm output, using the values that are entered in Low Alarm (CP-12), High Alarm
(CP-13), Ramped Error (CP-14) and Scaled Error (CP-15). See Figure 2-15. Refer to

Operations: Logic Control, Logic Output,

page 3-37 for details.

NOTE: This is an open-collector relay driver. Use an external DC power supply to

power the relays. Free-wheeling diodes are incorporated internally in the
ML-Drive and do not need to be added externally.

15

16

17

18

J4

EXTERNAL
DC
POWER
SUPPLY

(50V Max)

R1

R2

+V_DO

Drive Enable

Alarm

Common

+

WARNING

Do not exceed
the maximum current output of
150 mA for +5 VDC.

Exceeding the maximum
current output
can damage the ML-Drive.

Figure 2-15 Drive Enable and Alarm Outputs

Auxiliary DC Power

(J3 pin 1, 2)

The 5 volt output (J3 pin 1) is a DC regulated output that can be used to power
encoders or other auxiliary equipment that is used in conjunction with the ML-Drive. If
this output is used, it will nullify optical isolation.