PINKERTON Installer Manual

25


Name of
option

Address


Value allowed


Option Description

Entry delay

100

00 - 165
seconds

Sets the entry delay time. Applies to Entry Delay and
Handover Zones.

Exit delay

102

00 - 165
seconds

Sets the exit delay time. Applies to all Zones except 24hr
Zones.

Siren time

104

00 - 165
minutes

Sets the duration for the Siren output.

Test time

106

00 - 165 hours

Sets the time between test reports.

Test report
delay

246

00 - 165 hours

Sets the time by which the first test report will be delayed.
This delay commences from the first system reset after
power-up. See page 36, Automatic Test Reports.

Trim time

108

00 - 165
minutes

Reduces the time between test reports to adjust test report
time accuracy.

Squawk time

110

00 - 165
milliseconds

Sets the siren squawk duration. (Note, ON/OFF squawks are
of fixed length).

See page 24 for further information on siren squawks.