PSA PIN388D/PIN388L Installer Manual User Manual
Page 27
26
PINKERTON Installer Manual
Name of
option
Address
Value allowed
Option Description
General
options
240
Select 1, 4, 6, 7
1 Enable external inputs.
Enables the three additional inputs on the expansion pins
on the Pinkerton main board. These inputs are labelled
Panic, Duress and Test and are treated as normal Zone
inputs when enabled - resistors are required. Note that no
restoral reports are sent by these three inputs.
2 & 3 Zone Input Sensitivity
The response time of the Zone inputs can be increased to
allow the use of vibration sensors on one or more Zone
inputs. Turn lights 2 and 3 on or off to adjust for high,
medium or low sensitivity. Note that the setting will apply
to all Zone inputs.
Input sensitivity Light
2 Light
3
Normal (default) OFF
OFF
High
ON
OFF
Medium
OFF
ON
Low
ON
ON
4 Squawk
or
Flash.
Sets the option for either audible or visual indication of the
ON/OFF state of the system.
Light 4
Strobe flash On
Siren squawk Off
Address 098, option 6 must also be on for siren squawk
and strobe flash to work.
5 not
used
6 Zone 8 home key.
When selected, Zone 8 is used to turn the system ON in
home mode.
7 SIREN
TOGGLE
When selected, this option will cause any activation of
Zone 7 to toggle the siren ON and OFF. Note that if the
siren was triggered by an alarm condition, Zone 7 will not
toggle the siren OFF.
8 not
used
Attempts
before fail to
communicate
242
00 - 10
attempts
Sets the number of unsuccessful dialling attempts the system
will make before triggering Fail to Communicate. (Actions
triggered by Fail to Communicate are set at address 066).
Zone pulse
count
243
00 - 99 counts
Sets the number of Pulse Zones which may be triggered
before generating an alarm condition.
Zone pulse
time
244
00-165 seconds Sets the time during which the system will count triggers from
Pulse Count Zones.