• In addition to a room-protection system, localy

acting fire extinguishing systems (installed fixedly

and allocated to the object) shall give effective

protection for the hazard zone between the outlet

of coating materials and the workpiece. It shall be

proved for each individual case, if the aspects of

the locally acting fire extinguishing systems and the

room-protection system could be satisfied by one

fire extinguishing system.

• Electrostatic spraying systems shall be equipped

with locally acting automatic fire extinguishing sys-

tems which are actuated immediately in case of

fire. When the fire extinguishing system has been

activated, the high voltage supply, the supply of

coating materials and the pressurized air shall be

cut-off automatically.

EN 13478 shall be observed.

It shall be checked in each individual case, whether

a present room-protection system is also able to fulfill

the function of a locally acting automatic fire extin-

guishing system.

• Where conductive parts are used for the coating

material supply system, these parts shall be either

bonded to earth or connected with the high voltage

supply system so that the potential level is invari-

ably identical with that of the electrostatic spraying

system.

• Insure all earthed items are outside the safe use

distance of

204mm.

• In compliance with EN 12215: 2004

Effectivity of locally acting

fire extinguishing system

Conductive parts of the

spraying material supply

system

Minimum clearance

in air

Other tests

Evrey 6

months

Weekly

Weekly

In compliance

with

EN 12215:2004

SURVEY OF TESTS TABLE (Cont.)

Kind of Test

Requirements

Review & Testing

Interval

Aerobell 168 - Appendix

Ransburg

LN-9247-13

101