IAI America RCP2-CF User Manual

Page 120

Advertising
background image

100

Position-data table (Field(s) within thick line must be entered.)

No. Position

Speed

Acceleration/

deceleration

Push Positioning

band

Acceleration

only MAX

0

* * * * * *

1

30 100

0.3 0 0.1 0

2

10 20 0.3 0 0.1 0























T1:

6 msec or more; time after selecting/entering a command position until the start input turns ON

(The scan time of the host controller must be considered.)

Note 1: When the start signal turns ON, the position complete output will turn OFF and the moving

output will turn ON.

The start signal must be turned OFF with the confirmation that the moving output has turned
ON (position complete output has turned OFF) while the start signal remains ON.

If the start input remains ON as shown below, the position complete output will not turn ON
even when the actuator movement is completed.













Note 2: When a soft limit is reached as a result of repeated incremental moves, the actuator will stop

at that position and the position complete signal will be output.

=

Command position

Start

Position complete

Completed position

Moving




Actuator movement

Speed

Position 1

Position 2

T

1

T

1

Note 1

Note 2

Position 1

Position 2

Position 2

30 40 50 60 70

Time

Distance from home

Start

Position complete

Moving


Actuator

1 msec or less

Movement is complete.