Wiring the motor power cutoff relay

Explained below is a safety circuit conforming to safety category 2.
The user is responsible for implementing additional safety measures in the actual circuit configuration, such as
providing double contactor contacts to prevent fusing.

The circuit illustrated below is for reference purposes only.
 The input side of the motor drive power supply is connected to the MPI terminal, while the output side is

connected to the MPO terminal. Connect a contactor or other contact device to these terminals.

(Note) The rush current must be 8 A or less. The rated current is 2 A.
 The contact for the EMG switch on the teaching pendant is provided by the S1/S2 terminals.
(Note) When connecting the teaching pendant to a SIO converter, the contact for the EMG switch on the

teaching pendant is provided by the EMG1/EMG2 terminals on the SIO converter.




[Example of basic circuit]

































EMG switch

(Rush-in current: 8 A,
rated current: 2 A)

MC

24V

Teaching pendant

Motor power
supply

External EMG

reset switch

External EMG

circuit

PORT switch

(0.1 A)

Controller
power supply

Coil current:
0.1 A or less

(3 A)

ON

OFF

0V

MC

(MAX. 2 A)

MPO

MPI

S1

S2

24V

N

FG

RCP2 controller

MC