29

4.2.3

Wiring the Power Supply/Motor Power Cutoff Relay

(1)

Wiring the power supply











To connect multiple controllers, provide a relay terminal block.

Use a power cable satisfying the following specifications:

Item Specification

Applicable wire length

Single wire:

1.0 / Stranded: 0.8 mm

2

, AWG size 18 (copper wire)

Stripped wire length

10 mm

Temperature rating of
insulating sheath

60

C or above

* Use a flathead screwdriver with a blade tip of approx. 2.6 mm to push in the wire.


 Notes on wiring the absolute-specification controller

[1] When connecting a relay to the 24-V line, be sure to install it on the positive side of the 24-V power supply.

Keep the negative side of the 24-V power supply connected without cutting it off with a relay.
If a relay is installed on both the positive and negative sides, an ABS error may generate.


[2] Connect a surge killer to the relay contact.

Chattering of the relay may have negative effect on the controller.
Connect a surge killer to prevent malfunction.


Recommended product: Spark Killer by Okaya Electric

Industries

Model number:

CR-50500

Capacitance: 0.5

F  20%

Resistance: 50

 (1/2W)  30%









24V

0V

FG

S1

S2

MPI
MPO

24V

N

FG

Input power supply
24 VDC

(2 A max. per controller)

Surge killer

Relay

Do not install a relay on the negative side.

RCP2-
ABS

24V+

N

24VPS

AC