WRM-10P AND WRM-40 USER’S MANUAL

REV 3

16

3.2 General

Procedures

The main steps for using the WRM are outlined below:

a. Ground the WRM to the substation ground.

WARNING

Always connect the WRM to the substation ground before connecting any
test lead to any transformer bushing. Failure to follow this procedure may
damage the WRM.

b. Plug the WRM power cable into a power outlet.

c. Insert current-cable plugs and voltage-sensing cable plugs into the corresponding

control panel jacks.

d. Attach the test cable clamps to the transformer terminal for the winding that is to be

measured.

e. Turn on the WRM by pressing

[I]

on the power rocker switch.

f. The unit will self-calibrate, and then you will be presented with the “START-UP” menu as

shown below:

1. TEST XFMR 11/02/09

2. SETUP 12:33:01

3. USER DIAG