Vanguard WRM-40 User Manual

Page 27

Advertising
background image

REV 3 WRM-10P AND WRM-40 USER’S MANUAL

23

j. The WRM determines when the resistance reading is stable and displays the resistance

values on the LCD screen as shown below:

The WRM will continue the test and update the resistance values on the LCD screen.
While the test is in progress, you can press the

[ENTER]

key to save the current

readings from the LCD screen to the WRM’s internal working memory. This process can
be repeated as needed for a maximum of 48 times per test.

NOTE

Although this process can be used to store multiple readings when testing a
Load Tap Changer (LTC) or Voltage Regulator, a more convenient method is
also available. Please see section 3.5 for information about performing an
LTC or Voltage Regulator test.

If the

[ENTER]

key is pressed, the data is saved and the following screen will be

displayed on the LCD screen:

Once the data is saved, the following screen will be displayed:

Press the

[STOP]

key to stop running the test. The test results will be displayed as

shown:

Press any key to continue to the next step.

TEST RESULTS

I = 1.09A R1=499

μΩ

TEST SAVED

TEST IN PROGRESS

I = 1.09A R1=499

μΩ

TEST SAVED

* XFMR ENERGIZED! *

TEST IN PROGRESS

I = 1.09A R1=499

μΩ

SAVING TEST

* XFMR ENERGIZED! *

TEST IN PROGRESS

I=9.79A R1=499

μΩ

R2=105

μΩ

* XFMR ENERGIZED! *

Advertising