REV 3 WRM-10P AND WRM-40 USER’S MANUAL

31

g. The following screen will be displayed:

Use the

[PAPER Contrast]

and

[PAPER Contrast]

keys to adjust the D.U.T.

(Device Under Test) temperature.

Press the

[ENTER]

key to confirm the D.U.T. temperature setting.

h. The following screen will be displayed:

Use the

[PAPER Contrast]

and

[PAPER Contrast]

keys to adjust the

reference temperature.

Press the

[ENTER]

key to confirm the reference temperature setting.

NOTE

The WRM will calculate the equivalent resistance value at this new
temperature. Please see section 4.2 for further information about how this
value is calculated.

i. The following screen will be displayed:

Press any key to continue.

j. The following screen will be displayed:

Set the LTC or Voltage Regulator tap position as indicated on the LTC screen and press
the

[START]

key.

SET TAP TO 3 LOWER

“START” TO RUN TEST

OR

“STOP” TO ABORT

********WARNING******

DANGEROUS FLASH-OVER
WILL OCCUR IF CABLES

ARE DISCONNECTED!

D.U.T. TEMP

25.0

°C 77.0°F

↑↓ to adjust temp

“ENTER” to accept

REFERENCE TEMP:

85.0

°C 185.0°F

↑↓ to adjust temp

“ENTER” to accept