Vanguard WRM-40 User Manual

Page 24

Advertising
background image

WRM-10P AND WRM-40 USER’S MANUAL

REV 3

20

3.4

Performing a Resistance Test

a. Start from the “START-UP” menu:

Press the

[1]

key (TEST XFMR).

b. The following screen will be displayed:

Press the

[1]

key (V1 & V2 TEST) if you would like to perform a V1 & V2 test.

Press the

[2]

key (V1 ONLY TEST) if you would like to perform a V1 test only.

Please see section 3.5 for information about performing special tests.

NOTE

The test current is 10 Amps for the WRM-10P and 40 Amps for the WRM-40.

c. The following menu will be displayed:

Press the

[2]

key (NO).

d. The following screen will be displayed:

1. YES

Press the

[1]

key (YES) if you wish to convert readings to standard temperature.

The following screen will be displayed:

LTC or VTG REG?
1. YES

2. NO

WINDING MATERIAL:
1. COPPER, Tk=234.5

2. ALUMINUM, Tk=225

3. MANUALLY ENTER Tk

CONVERT READINGS

TO STANDARD TEMP?

1. YES

2. NO

1. V1 & V2 TEST

2. V1 ONLY TEST

3. SPECIAL TEST V1,V2

4. SPECIAL TEST V1

1. TEST XFMR 11/02/09

2. SETUP 12:33:01

3. USER DIAG