WRM-10P AND WRM-40 USER’S MANUAL

REV 3

32

k. The following screen will be displayed momentarily:

After the WRM finishes its internal calibration, the following screen will be displayed:

l. The WRM determines when the resistance reading is stable and displays the resistance

values on the LCD screen as shown below:

Press the

[ENTER]

key to accept and save the readings.

m. The following screen will be displayed:

Once the reading has been saved, the following screen will be displayed momentarily:

n. After saving the readings, the following screen will be displayed:

Set the LTC or Voltage Regulator tap position to the position indicated on the LCD screen
and press the

[START]

key.

The WRM will continue the test and display the results as in step l. Repeat steps l
through m
for all “Lower” positions and then through all “Raise” positions.

SET 2L THEN “START”

* XFMR ENERGIZED! *

TEST IN PROGRESS 21

I=0.01A R1=997.4

μΩ

TEST SAVED

* XFMR ENERGIZED! *

TEST IN PROGRESS 21

I=0.01A R1=997.4

μΩ

SAVING TEST

* XFMR ENERGIZED! *

TEST IN PROGRESS 21

I=0.01A R1=997.4

μΩ

R2=0

μΩ

* XFMR ENERGIZED! *

XFMR CHARGING

PLEASE WAIT…

I = 0.03A

* XFMR ENERGIZED! *

CALIBRATING

PLEASE WAIT...