Proface APL3000B - Node Box PC User Manual

Page 106

Advertising
background image

Chapter 6 PS-A Monitoring Features

6-5

‹ LED Indicator

‹ External Input Signals

The PS-A’s RAS interface connector uses the following input signals.

General Purpose Input (DIN 2 bits)

This standard digital input is used for alarm detection in external devices. The input signal uses two bits.

The System Monitor property of the control panel or the API-DLL can be used to enable or disable this

feature, as well as designate what type of processing is to be performed once a signal is received. (Only

the “ON” state of the DIN circuit is detected. The “OFF” state of the DIN circuit cannot be monitored.)

Remote Reset Input (Available with DIN1 only)

This is the reset signal sent from an external device to the PS-A. When this signal is enabled, a forced

reset of the PS-A is performed.

The System Monitor property of the control panel or the API-DLL can be used to enable or disable this

feature.

LED Color

System Status

Output Condition

Green (Lit)

Normal Operation (Power is ON)

None

Green (Blinking)

System is NOT running (Soft OFF)

None

Orange (Lit)

A RAS alarm has occurred.

LED is enabled via System
Monitor Property.

Touch Panel Self-Test Error

None

Not Lit

Power is OFF

-

Orange/Red (Blinking)

Backlight error

None

To enable Remote Reset Input, make sure to check the [Enable] in the [Remote reset] tab of

System Monitor Property. For Remote Reset of System Monitor Property, refer to the following.

Input Voltage

DC12V to DC24V

Input Current

10mA

Operating Voltage

ON voltage: 10V (min), OFF voltage:3V (max)

Isolation Method

Via photocoupler

SEE

6.8.4 Remote Reset (page6-31)

Advertising