PS-3650A / PS-3651A User Manual

3-12

3.2.3

Grounding

This section describes the precautions for grounding the PS-A unit.

• When supplying power to the PS-A unit, be sure to

separate the input/output and power lines, as shown.

[diagram (a)]

• If exclusive grounding is not possible, use a common

connection point. [diagram (b)]

3.2.4

I/O Signal Line Placement

Input and output signal lines must be separated from the power control cables for operating circuits.

If this is not possible, use a shielded cable and ground the edge of the shield.

Do not use common grounding, since it can lead to an accident or machine breakdown.

• Check that the grounding

resistance is 100

Ω or less.

• FG and SG terminals are

internally connected in the PS-A.

When connecting an external

device to the PS-A using the SG

terminal, be sure to check that

no short-circuit loop is created

when you setup the system.

• The grounding wire should have

a cross sectional area of 2mm

2

or greater. Create the connection

point as close to the PS-A unit as

possible, and make the wire as

short, as possible. When using a

long grounding wire, replace the

thin wire with a thicker wire, and

place it in a duct.

If the equipment does not function

properly when grounded, disconnect

the ground wire from the FG terminal.

(a) Exclusive Grounding (BEST)

(b) Common Grounding (OK)





(c)Common Grounding (Not OK)

PS-A Unit

Other

Equipment

PS-A Unit

Other

Equipment

PS-A Unit

Other

Equipment