6.3.5 Current Output During Alarm Occurrence

• The current output and display values during alarming can be selected in advance.

Display

Description

Set a value for current output to be used during alarms in parameter number "11"

Code

Contents

00

01

02

03

2.4mA or less

4.0mA

Hold

21.6mA or more

Default: 00
(2.4 mA or less)

6.3.6 Reversing Flow Direction

• The flow direction is set to “FORWARD” at the factory. This function enables to set

flow direction from “FORWARD” to “REVERSE”.

*

Note that measurements cannot be made both in reverse and forward directions.

Display

Description

Set the flow direction in parameter "14".

Code

Contents

00

01

Forward direction

Reverse direction to flow arrow

Default: 00

6.3.7 Limiting on Current Output

(1) 4 to 20 mA Low Cut Output (Current Output near by 0% Range)

• This function makes it possible to reduce noise in the 4mA region to reduce it
to 0%.

Display

Description

Setting range : 0 to 10%

0.5% 0.5%

4mA

5.6mA(10%)

Output

Set value

Input

Hysteresis: 1% fixed

Default: 0(%)