Yokogawa ADMAG CA User Manual

Page 60

Advertising
background image

IM 1E8B0-01E

7-10

7. OPERATION VIA BRAIN TERMINAL

7.2.4

Display of Internal Totalization (Refer to 6.3.2)

Example : 10 L (liter) output per pulse in a flow rate span of

ٗٗٗ m

3

/h

Display

Description

Code

Volume unit

n UNIT/P

µ

UNIT/P

m UNIT/P

UNIT/P

k UNIT/P

M UNIT/P

PULSE/s

Volume unit used in 10

-9

×

flow rate span

Volume unit used in 10

-6

×

flow rate span

Volume unit used in 10

-3

×

flow rate span

Volume unit used in 1

×

flow rate span

Volume unit used in 10

3

×

flow rate span

Volume unit used in 10

6

×

flow rate span

Number of pulses output per second at 100% of output

Example) When pulses are to be output per L(liter) in a span of

ٗٗ

m

3

/h, select “m UNIT/P” since a L =10

-3

×

m

3

Set the pulse weight “10 (L)” in parameter number “E02.”

Set the low cut range percentage in parameter “E03.” Range of setting : (0 to
100% of span)

Select instantaneous flow rate or flow rate after damping for the pulse output.
(The damping time value is the value set in “B02.”)
Default: DAMP (damped flow rate data)

Select the volume unit for the pulse weight in parameter number “E01.”

PARAM
E01:TOTAL UNIT
m UNIT/P
E02:TOTAL SCALE
10 m UNIT/P
E03:TOTAL LOWCUT
3. %

DATA

ESC

DIAG

PARAM
N01:TOTAL/PULSE
DAMP
N02:PULSE MODE
ON
N03:RATE LIMIT
5. %

DATA

ESC

DIAG

* The "N" item can be opend by entering "55" in parameter number "L02".