IM 1E8B0-01E

7-9

7. OPERATION VIA BRAIN TERMINAL

7.2.3

Pulse Output (Refer to 6.3.1)

Example setting : 10 liter output per pulse in a flow rate span of

ٗٗٗ m

3

/h

PARAM
F01:PULSE UNIT
m UNIT/P
F02:PULSE SCALE
10 m UNIT/P
F03:PULSE LOWCUT
3. %

Display

Description

Code

Content

PULSE OUT

ALARM OUT

Pulse output
Alarm output

Code

Volume unit

n UNIT/P

m UNIT/P

m UNIT/P

UNIT/P

k UNIT/P

M UNIT/P

P ULSE/s

Volume unit used in 10

-9

5 flow rate span

Volume unit used in 10

-6

5 flow rate span

Volume unit used in 10

-3

5 flow rate span

Volume unit used in 1 5 flow rate span

Volume unit used in 10

3

5 flow rate span

Volume unit used in 10

6

5 flow rate span

Number of pulses output per second at 100% of
output

Code

Pulse width

50%DUTY

0.5ms

1ms

20ms

33ms

50ms

100ms

Example) When pulses are to be output per same liter in a span of m

3

/h,

select "m UNIT/P" since a L(liter) = 10

-3

×

m

3

Set the low cut range percentage in parameter "F03".
Range of setting : (0 to 100% of span)

Select "Pulseoutput" in parameter number "B10".

Select the volume unit for the pulse weight in parameter number "B04".

Select the pulse width in parameter number "F04"

Set the pulse weight "10 (L)" in parameter number "F02".

*Since parameter number "F02" is a 5-digit data item, scrolling is

necessary to display all the data. Mind the decimal point when seting are

made. (The decimal point can be moved if required.)

(Max. of 1000P/s

Min. 0.0001P/s)

(Max. of 1000P/s

Min. 0.0001P/s)

(Max. of 500P/s

Min. 0.0001P/s)

(Max. of 25P/s

Min. 0.0001P/s)

(Max. of 15P/s

Min. 0.0001P/s)

(Max. of 10P/s

Min. 0.0001P/s)

(Max. of 5P/s

Min. 0.0001P/s)

PARAM

B10:PULSE/ALARM

PULSE OUT
B11:4-20mA OR LESS
2.4mA OR LESS
B12:POWER FREQ
50.03Hz

DATA

ESC

DIAG

DATA

ESC

DIAG

PALAM
F02:PULSE UNIT
10 m UNIT/P
F03:PULSE LOWCUT
3. %
F04:PULSE WIDTH
50% DUTY

DATA

ESC

DIAG

ESC

Nor mally, these are all required settings.

The following settings are made depending on the application that is used.

Select instantaneous flow rate data or damped flow rate data for the pulse
output calculation.
(The damped value is the value set in “B02”.)

Set parameter “N02” to “OFF” when the pulse output transistor is to be
active in the off mode.

PARAM
N01:TOTAL/PULSE
NO DAMP
N02:PULSE MODE
ON
N03:RATE LIMIT
5. %

DATA

ESC

DIAG

* The "N" item can be opend by entering "55" in parameter number "L02".