8 alarm output, Alarm output -11 – Yokogawa ADMAG CA User Manual

Page 48

Advertising
background image

IM 1E8B0-01E

6-11

6. FUNCTION AND DATA SETTINGS

(2) 4 to 20 mA Low Limit

• This function limits the low end of the 4 to 20mA output.
• The default value is -20%, but a -8% (2.72mA) limit is provided to cope with reverse

fluid flow. When a lower setting is required, change this value.

• 2.4mA or less output in alarming is also limited.

Display

Description

Setting range: -20 to 100%
Default: –20(%)

4mA

Output

5.6mA(10%)

Default: –20(%)

(3) 4 to 20 mA High Limit

• This function limits the high end of the analog output.
• The default value is 110% (21.6mA). Please set in case other setting is required.
• 21.6 mA or more output in alarming is also limited.

Display

Description

Setting range : 0 to 110%

18.4mA(90%)

4mA

Output

Default: 110(%)

6.3.8 Alarm Output

• This function outputs a signal from the P+ and P- terminals when an alarm occurs.

These terminals are also used for pulse output and cannot be used for this
function when they are outputting pulses.

• The contact goes from close to open (OFF) during alarming.

Display

Description

Code

Content

00

01

Pulse output

Alarm output

Set "01" in parameter number "10" to use the P+ and P- terminals for alarm

output.

Initial setting : 00

(pulse output)