4.2.1. Procedure to measure insulation resistance in any modes
1. Select the desired mode by means of the

FUNC key.

2. Connect the black and blue cables to the instrument input terminals

B1 and B4

respectively

Fig. 3 Insulation P-PE with untied cables

Fig. 4 Insulation P-PE with Shuko cable


3. If the cables supplied with the instrument are not long enough for the measurement you can

extend the blue cable.

4. Connect the instrument terminals to the object which is to be submitted to the insulation

test

after disconnecting the circuit under test and all the relative loads (see Fig. 3,

Fig. 4)


5. By

means

of

U

n

/I

n

select the test voltage suitable for the type of test

to be carried out (see table). The values to be selected are:
 50V (test on telecommunication system)
 100V

 500V

 250V

 1000V

Standard

Brief description

Test voltage

Maximum limit value

CEI 64-8/6

Systems SELV or PELV

Systems up to 500V (Civil installations)

Systems over 500V

250VDC
500VDC

1000VDC

> 0.250M

> 1.000M

> 1.000M

EN60439

Electrical panel boards 230/400V

500VDC

> 230k

EN60204

Electrical equipment of machines

500VDC

> 1M

Table 1: Test voltage values and limit values for the most common kinds of test

CAUTION

If

“Measuring” is displayed the instrument is effecting the measurement.

During this phase do not disconnect the test leads as the circuit under test
may remain charged at a dangerous voltage due to the parasite capacities of
the installation. Independently of the working mode selected the instrument
throws a resistance in the output terminals at the end of each test to
discharge the parasite capacities of the circuit.