Caution – HT instruments SIRIUS87 User Manual

Page 35

Advertising
background image

SIRIUS

87

EN - 33

4.4. LOOP :

LOOP IMPEDANCE, FAULT CURRENT AND PHASE
SEQUENCE TEST

Turn the

switch on LOOP

position.

Switch on the instrument.

The key

FUNC permits to select one of the following measuring modes

(which can be shown cyclically when pressing the key):

 Mode “

P-N” (the instrument measures the resistance between the phase

and neutral conductors and calculates the phase to neutral prospective
short circuit current).

 Mode “

P-P” (the instrument measures the resistance between two phase

conductors and calculates the phase to phase prospective short circuit
current).

 Mode “

P-PE” (the instrument measures the resistance between the

phase and protective conductors and calculates the phase to earth
prospective short circuit current).

 Mode “

” (the instrument detects the phase sequence and measures

the three delta voltages: L1-2, L2-3, L3-1).

CAUTION

The display of

“Measuring” means that the instrument is measuring. During

this phase never disconnect test leads.





















FUNC