Vol ag – HT instruments SIRIUS87 User Manual

Page 42

Advertising
background image

SIRIUS

87

EN - 40

4.4.6. Anomalous cases which may occur during LOOP

tests in any working mode

 Should the instrument detect that the

phase and/or neutral cables are not
connected to an installation, screen
alongside is displayed when pressing
START/STOP.

LOOP



P-N

VOL AG

 This screen is displayed when system

the phase conductor was reversed with
respect to the neutral.

LOOP



 A

P-N

 This screen is displayed when the

phase conductor was reversed with
respect to the earth.

LOOP



 A

P-PE

 Should the instrument detect a voltage

between phase and neutral higher of
265V, for example in case the blue
cable is connected to an installation
phase conductor of a 400V three-phase
system, the screen alongside is
displayed.

LOOP

Hi

P-N

VOL AG

 This screen is displayed when in

biphase system the blue conductor was
reversed with respect to the green one.

LOOP

 A

PEN


THE PREVIOUS RESULTS CANNOT BE SAVED.


Message

"no VOL tAG”: a
too low voltage
was detected.

The instrument does not effect the test.
Reverse the shuko plug and exchange the black
cable with the blue one. Check the earth
connection. Repeat the test.

The instrument does not effect the test.
Reverse the phase to earth connection in the plug
under test or exchange the black cable with the
green one. Repeat the test.

The instrument does not effect the test.

Message

“Att”:

too low voltage
between phase
and earth.

Message

“Att”:

too low voltage
between phase
and neutral.

Message

“Hi

VOL tAG”: a too
high voltage was
detected.

SAVE

Advertising