HT instruments SIRIUS87 User Manual
Page 20
SIRIUS
87
EN - 18
4.2.1.2. Mode
"TIMER"
6. Use the following keys to set the duration time of the test:
Press this key to increase the duration time of the test (
Tmax=999 seconds).
Press this key to decrease the duration time of the test (
Tmin=10 seconds).
7. Press
the
START/STOP key.
The instrument effects the measurement ending when the set time has elapsed.
999 seconds
Maximum value of the test duration.
10
seconds
Minimum value of the test duration.
Note: Pressing the START/STOP key again the test gets immediately interrupted.
At the end of the test, in case the
resistance value R
ISO
detected results
to be lower than R
MAX
(depending on
the selected voltage see following table)
and the test is effected at the selected
rated voltage value, the instrument
emits a
double sound signal indicating
the positive outcome of the test
displays one screen similar to the screen
alongside.
R
ISO
2.07
M
500 V 20
s
TIMER
The values of measured resistance of isolation always must be confronted with the
normative limits for being able to assert if the system is to norm.
SAVING:
The test can be stored pressing the
SAVE key twice
(according to § 5.1).
Note: The maximum resistance value R
MAX
which can be measured in mode M
depends on the rated voltage selected for the test. In particular:
Rated voltage selected
for the test
R
MAX
= Maximum resistance
value
50VDC
99.9M
100VDC
199.9M
250VDC
499M
500VDC
999M
1000VDC
1999M
Table 2: Test maximum resistance values depending on the rated voltage selected
Timer mode.
Duration of the
set test.
Insulation
resistance value
R
ISO.
Rated voltage value selected for the Timer test.
SAVE
START
STOP