HT instruments SIRIUS87 User Manual

Page 43

Advertising
background image

SIRIUS

87

EN - 41

 If the instrument detects that the earth

cable (green) is not connected, the
screen alongside is displayed for 5
seconds then the initial display is back.
Check the connections of PE conductor
under test.

LOOP



>

1999




no

PE

 If a contact voltage U

t

higher than the

selected limit (U

L

) is detected the

instrument

interrupts the test and emits

a long sound signal at the end of the
test and displays the values
alongside.displays the screen
alongside.

LOOP

>

50

V

A

UL

t

U

L

=50V

 If during the test the instrument detects

a lack of voltage the screen alongside
is displayed.

LOOP



 c

P-P

- - - - - -

t

 If the thermistores of the instrument are

damaged, it displays the screen
alongside.

LOOP



c

 If the instrument gets overheated it

does not permit to effect the tests and
displays the message alongside. Wait
until the instrument displays the initial
screen before proceeding with
measuring.

LOOP




THE PREVIOUS RESULTS CANNOT BE SAVED.

Message

“no PE”: the

instrument does
not detect the
protection circuit.

Messagge

“hot”:

the instrument is
overheated.

P-P or P-N
or P-PE

Message

"Att

UL":
a too high
contact voltage
was detected

Message

">50" o “>25V”: the instrument detects

a contact voltage higher than the selected limit
(50V in this case).

The instrument
can display 0° or
180°

SAVE