HT instruments SIRIUS87 User Manual

Page 26

Advertising
background image

SIRIUS

87

EN - 24

4.3.1.1. Mode "MAN x½"

4.

 Press the

START/STOP key once. The instrument carries out the

test injecting a current in phase with positive half wave of the
voltage indicated on

display by 0°.

 Press the

START/STOP key twice. The instrument carries out the

test injecting a current in phase with negative half wave of the
voltage indicated on

display by 180°.

 If the RCD does NOT trip the

instrument emits a

double sound

signal indicating the positive
outcome
of the test and displays the
screen alongside.

RCD

~



>

999

ms

OK

N

30

m

A

2

V

x1/2

MAN

0° U

L

=

50

V


SAVING:

The test can be stored pressing the

SAVE key twice

(according to § 5.1).


Value of contact
voltage

U

t

detected referred
to the rated value
of the RCD
current set.

OK: indicates that
RCD passed the
test.

The symbol

">" means that the RCD did not trip.

Indicates if the test was carried out with current
phase 0° or 180° with respect to the voltage.

or RCD

SAVE

START

STOP

Limit set for the
contact voltage