Vol ag – HT instruments SIRIUS87 User Manual

Page 21

Advertising
background image

SIRIUS

87

EN - 19

4.2.2. Special cases which may occur during the tests "MAN", "AUTO", "TIMER"

 In case a value of R

ISO

higher than

R

MAX

was detected (depending on the

selected voltage see following Note
table, the instrument emits a

double

sound signal at the end of the test
indicating the positive outcome of the
test
and displays one screen similar to
the screen alongside.

R

ISO



> 999

M

500 V 20

s


MAN

 In case a test is effected at a voltage

lower than the set rated voltage, at
the end of the test the instrument emits
a

long sound signal and displays one

screen similar to the screen alongside.

R

ISO



0.01

M

500 V 20

s


MAN


SAVING:

The test can be stored pressing the

SAVE key twice

(according to § 5.1).


 If the terminal voltage is higher than

30V, the instrument does not effect the
test, displays the screen alongside for 5
seconds after which, it shows the
default screen relative to the R

ISO

test

under selected mode.

R

ISO



 33V

VOL AG


THIS RESULTS CANNOT BE SAVED.

ATTENTION: the
test was not
carried out.
Check that the
circuit is not
energised.

The symbol

">"

means that the
resistance value
R

ISO

is higher than

R

MAX

Test duration

Selected mode
MAN

Selected mode
MAN

ATTENTION: the test of resistance R

ISO

was

effected at a voltage value lower than the set
rated voltage
. Low insulation case. This case
occurs under low insulation conditions or in the
presence of capacity on the installation.

Maximum resistance value which can be
measured (999

 is displayed if a rated voltage of

500V was selected see table).

SAVE

SAVE