d) The instrument effects the test at I

n

180°. Follow the same

procedure as described under c).

e) The instrument effects the test at 5I

n

0°. Follow the same

procedure as described under c).

f) The instrument effects the test at 5I

n

180°. Follow the same

procedure as described under c). The test is completed.

In case of AUTO working mode the operator shall switch the RCD on
whenever the instrument displays the blinking symbol

“rcd” signaling the

RCD tripping.

Note: On selective RCDS it is possible to carry out the following tests ”Man ½ I

n

”, ”Man

1 I

n

”, ”Man 2 I

n

”, ”Man 5 I

n

”, “AUTO”.


The key

U

L

permits to select one of the following limit values for the

contact voltage (which can be shown cyclically when pressing the key):
 50V (default)
 25V.


CAUTION

The display of

“Measuring” means that the instrument is measuring. During

this phase never disconnect test leads.



Note: ”Man 5 I

n

” and “AUTO” test modes aren’t available for RCD type A

500mA.