SIRIUS

87

EN - 67

- Tripping time (t

N

)

Measuring range (ms)

Resolution (ms)

Accuracy

½ I

N

, I

N

1

999

2 I

N

1

200 general

1

250 selective

5 I

N

RCD (*)

1

50 general

1

160 selective

1

(2% rdg + 2 dgt)

(*) ”Man 5 I

n

” and “AUTO” test modes aren’t available for RCD type A

500mA


- Earth resistance R

A

without RCD tripping

Measuring range (

) Resolution

(

)

Accuracy

1

 1999

1

-0%, +(5% rdg + 3 dgt)

Test current

0.5 I

N

set in U

t

test mode

15mA in Ra 15mA test

- Tripping current for RCD type A and AC

General RCD with I

N

 10mA

RCD type

Measuring range I

N

(mA)

Resolution (mA)

Accuracy

AC

(0,5

 1,4) I

N

0,1 I

N

-0%, +10% I

N

A

(0,5

 2,4) I

N

General RCD with I

N

 10mA

RCD type

Measuring range I

N

(mA)

Resolution (mA)

Accuracy

AC

(0,5

 1,4) I

N

0,1 I

N

-0%, +10% I

N

A

(0,5

 2) I

N


- AC voltage

Measuring range (V)

Resolution (V)

Accuracy

0

 460

1

(3% rdg + 2 dgt)


- Frequency

Measuring range (Hz)

Resolution (Hz)

Accuracy

47,0

 63,6

0,1

(0,1% rdg + 1 dgt)


- Line impedance (phase to phase or phase to neutral)

Measuring range (

) Resolution

(

) (*)

Accuracy

0,01

 19,99

0,01

(5% rdg + 3 dgt)

20,0

 199,9

0,1

(*) 0.1m

 in the range 0.0  199.9 m (with IMP57)

Max peak test current

127V

3,65A

230V

6,64A

400V

11,5A

Phase to phase test voltage

100

 460V 50Hz 0,5Hz

Phase to neutral test voltage

100

 265V 50Hz 0,5Hz


- Fault loop impedance (phase to ground)

Measuring range (

) Resolution

(

) (*)

Accuracy

0,01

 19,99

0,01

(5% rdg + 3 dgt)

20,0

 199,9

0,1

200

 1999

1

(*) 0.1m

 in the range 0.0  199.9 m (with IMP57)

Max peak test current

127V

3,65A

230V

6,64A

Phase to earth test voltage

100

 265V 50Hz 0,5Hz