Con ins – HT instruments SIRIUS87 User Manual

Page 36

Advertising
background image

SIRIUS

87

EN - 34

4.4.1. High resolution Impedance measurement (0.1m

)

SIRIUS 87 is connectable to an external

optional accessory (IMP57) useful for high resolution

impedance measurement close to a power transformer.
The high Resolution impedance measurement is available inside the

LOOP P-P, P-N, P-PE

modes by mean

Un/IΔn key.

If You enable the High Resolution Impedance Measurement mode without connecting IMP57
the following screen will be displayed:

LOW

LOOP



no


con ins


For further details regarding IMP57 use and technical characteristics please refer to IMP57 user
manual or HT web site

www. ht-instruments.com.


4.4.2. Mode "P-N"
1. Select

P-N mode by means of the FUNC key.

2. If possible disconnect all low impedance loads downstream the point at which the

measurement is to be taken, as such an impedance would be in parallel with the line
impedance to be measured.

3. Connect the 3 black, blue and green connectors of the three-terminal shuko cable or of the

single cables in the corresponding input terminals of the instrument

B1, B3, B4 (see Fig. 9,

Fig. 10). When using untied cables connect the crocodiles to the free ends of the cables.

Fig. 9: Connection for P-N impedance

measurement Single/Two phase 230V

Fig. 10: Connection for P-N impedance

measurement Three-phase 400V